Skip to content
HeatAlgo
BlogGuides

Heating glossary for homeowners: what your installer's form asks for

A heating glossary for homeowners: floor plans, sections, window schedules, U-factor, R-value and radiant floor heating - what each is and where to find it.

Founder of HeatAlgo, author of the calculation engine to EN 12831 and EN 1264

Your installer has sent a form asking for "floor plans", "sections" and a "window and door schedule". This glossary explains what each of those words means, why anyone wants that information and where to look for it. The entries stand alone - read only the one you got stuck on.

If you do not have something, that is not a problem: almost every item can be replaced by a measurement or a photo. You can also fill in part of the form and come back to it later.

One thing to know up front. Your installer's tool, HeatAlgo, calculates heat loss room by room to the European standard EN 12831-1 and radiant floor output to EN 1264. If your installer's account is set to imperial units, the app shows feet, ft², °F and Btu/h; the calculation itself always runs in metric, to those standards.

The documents your installer asks for

What each document gives

Floor plan
Room layout and dimensions, floor areas, and where the windows and doors are.
Building section
Ceiling heights and how the floors stack - this is where heated volume comes from.
Window and door schedule
The size of every window and door, often with the U-factor.
Architectural drawings
Wall, floor and roof assemblies: what is in them, and how thick.
Energy rating or audit
U-factors or R-values for the assemblies and the air leakage assumptions.
DWG or DXF files
The same plan in vector form - dimensions read off without redrawing.
None of these is required. Each one shortens the work and cuts the number of assumptions someone has to make for you.

The drawings beside each entry are examples, drawn the European way, as in the houses HeatAlgo was built around. Your own documents will look different - different tags, a different sheet layout, dimensions in feet and inches - because every architect draws their own way. They are here so you can tell which document is meant, not to compare line by line.

Floor plan

A drawing of one story seen from above - as if the house were cut through about 3 feet above the floor and you looked down. It shows the room layout, room dimensions and where the windows and doors are. There is usually one per story: basement, first floor, second floor, attic. You will find them in the architectural drawings.

What a floor plan looks like

Example

Floor plan of a detached house: hatched walls, room names, window and door symbols with swing direction, staircase.
The hatched bands are walls cut through, the arcs at the doors show which way they swing, and the gaps drawn with a double line are windows.Drawing: Wikimedia Commons, public domain.

Building section

A drawing of the building cut vertically, from foundation to roof. A floor plan shows what is next to what; a section shows what is above what. Ceiling height comes from here, and from that the volume of air that has to be heated. It sits in the same set of drawings as the plans.

What a section looks like

Example

GradeAtticFirst floor8 ft 10 in8 ft 2 inRidge
The green dimensions on the right are exactly what an installer opens a section for: the height of each story.Illustrative drawing by HeatAlgo.

Window and door schedule

A table of every window and door: tag, size, quantity, often the U-factor. It sounds like paperwork and is one of the more important items - a large share of heat escapes through windows, so without their sizes the calculation would rest on assumptions. For a finished house, the window labels or a tape measure will do.

What a window schedule looks like

Example

TagSize (W x H)QtyU-factor
W159 x 55 in30.16
W294 x 87 in10.14
W324 x 24 in20.19
D139 x 83 in10.23
The tags (W1, W2, D1) point back to the floor plan - the same windows, marked the same way on both drawings. The last column is the U-factor in Btu/h·ft²·°F that goes into the calculation.Illustrative drawing by HeatAlgo.

Architectural drawings

The set of drawings and descriptions the house was built from. The most valuable part for an installer is the description of the assemblies: what a wall is made of, in what order and how thick. That is what decides how well the wall holds heat.

How a wall assembly is stated - an example, a masonry wall with exterior foam insulation, layers from inside to outside:

LayerThicknessR-value (h·ft²·°F/Btu)
Interior plaster0.6 in-
Clay block9.4 inabout 5.5
EPS foam insulation7.9 inabout 28.4
Exterior stucco0.2 in-
Whole wall, 18.1 inabout R-35, U-factor 0.028 Btu/h·ft²·°F

In this wall the insulation takes up nearly half the thickness and gives almost all of the R-value. The energy rating sample below lists the same wall at 0.028.

Structural drawings

Drawings of the structure: foundation, floor framing or slabs, roof trusses. Needed less often, but useful for radiant floor heating, because they say what the floor rests on and how much can be built up on top of it.

Energy rating or energy audit

A document stating how much energy the house uses and how its parts perform. In Europe it is the energy performance certificate, produced on sale, letting or handover; in the US the closest documents are a HERS rating or an energy audit report. For an installer it is mainly a shortcut: it often lists the U-factors or R-values of the assemblies and the air leakage assumptions. It does not replace the calculation used to size equipment, but it can speed it up a lot.

What an installer looks for in a rating

Example

Energy performance certificate

Building energy class

Assembly data (U-factor, Btu/h·ft²·°F)

Exterior wall
0.028
Roof
0.023
Slab on grade
0.049
Windows
0.16

Not the colored band, but the table under it - U-factors that would otherwise have to be dug out of the drawings.

This sample is a European certificate. The energy class is its best-known part and the least useful one for sizing equipment. The assembly table is where the value is.Illustrative drawing by HeatAlgo.

DWG and DXF files

Technical drawing formats from CAD software. Unlike a PDF or a photo, they carry real dimensions that can be read off without redrawing. If your architect handed over the drawings in these files too, they are worth attaching.

Terms about the house

Building assembly

Anything separating the heated interior from something colder: exterior wall, roof, floor over a basement or crawlspace, slab on grade, window, door. Your installer calculates the heat loss through each one separately. In HeatAlgo these are called building elements.

Assembly layers

A wall is rarely one material. A typical one has drywall or plaster, a structural layer (framing, block, brick, concrete), insulation and an exterior finish. Order and thickness matter - they decide how much heat escapes. If you do not have the drawings, anything helps: a photo from the build, an insulation invoice, what the builder remembers.

Insulation and R-value

The layer meant to keep heat inside: foam board (EPS, XPS, polyiso), mineral wool, fiberglass, spray foam. Two things matter for the calculation: what was used and how thick it is - together they give the R-value. Higher R is better. The difference between 2 and 8 inches of foam board is several times the heat loss through the wall - and often a whole equipment size.

Window U-factor

The number on a window's label saying how much heat it lets through. Lower is better. In the US it is printed on the NFRC label in Btu/h·ft²·°F; a European window's data plate gives the same thing as Uw in W/(m²·K).

Typical U-factors, from worst to best:

WindowU-factor (Btu/h·ft²·°F)Uw (metric)
Old wood window, single glazing0.88 Btu/h·ft²·°F5.0
Double glazing from the 1990s0.46 Btu/h·ft²·°F2.6
Modern double glazing0.19 Btu/h·ft²·°F1.1
Triple glazing0.14 Btu/h·ft²·°F0.8
Polish building code limit for a vertical window, since 20210.16 Btu/h·ft²·°F0.9

These are indicative values. Your own windows have their U-factor on the label or in the window schedule - that is the number that goes into the calculation.

Heated floor area and volume

Heated floor area is the square feet of floor in the rooms that are actually heated - excluding the garage and an unheated basement. Volume is the space those rooms enclose, area times ceiling height. Floor area drives radiant floor heating; volume drives ventilation.

Stage of the project

Your installer asks because it decides where the data comes from. At design stage everything is in the drawings. During construction some things can still be measured and changed. In a finished house the data is reconstructed from measurements and documents - and that is where an energy rating or audit helps most.

Terms about the system

Radiant floor heating and radiators

Radiant floor heating gives off heat across the whole floor area, so it works with low water temperatures (86 °F-104 °F) - which pairs well with a heat pump. Radiators give off heat from a small surface, so they need hotter water (113 °F-158 °F) and respond faster to a change of setting. Mixed systems are normal: radiant floors downstairs, radiators upstairs.

Manifold

The box where all the radiant floor loops meet - water leaves for the rooms here and returns here. Flow is set for each loop separately at the manifold, so each room gets as much heat as it was calculated to need.

Air-to-water and ground-source heat pumps

Air-to-water takes heat from the outdoor air - cheaper to install, no digging, but its efficiency drops in a cold snap. Ground-source (often called geothermal) takes heat from the ground through wells or a horizontal loop field - more expensive up front and it needs either yard space or drilling, but it runs steadily whatever the weather.

Ventilation: natural, exhaust-only, heat recovery

Natural ventilation relies on leaks and stack effect - no equipment, but no control over how much air escapes either. Exhaust-only ventilation pulls air out with a fan (a bath fan running continuously, for example). Heat recovery ventilation, with a heat recovery ventilator (HRV), is balanced mechanical ventilation that reclaims heat: outgoing air warms the incoming air. The choice weighs heavily in the calculation, because ventilation is one of the two main routes heat takes out of a house.

Comfort temperature

The temperature you want in a room - and a real input to the calculation, not a survey about preferences. The system is designed around specific values, usually about 68 °F-70 °F in living rooms and 75 °F in a bathroom. If you like it warmer, say so at the start, not after installation.

Terms most often confused

Four pairs that are easy to mix up

  • Heated floor area

    Square feet of floor in the rooms that are heated.

    Volume

    The space those rooms enclose - area times ceiling height.

    Two homes with the same floor area, one with sloped ceilings and one with 10 ft ceilings, have different volumes and different heat loss.

  • Equipment output (Btu/h)

    How much heat the heat pump delivers in the coldest hour of the year.

    Annual use (kWh)

    How much energy the system uses across a season.

    The first number decides which unit to buy. The second decides what running it costs you.

  • Energy rating

    A document stating annual energy use and how the house performs.

    Heat loss calculation

    The heat the house needs, worked out room by room.

    A rating can be a good source of data, but it is not enough to size a heat pump or radiators.

  • Floor plan

    A story seen from above. Shows what is next to what.

    Section

    The building cut vertically. Shows what is above what.

    Areas come from the plan, heights from the section. The calculation needs both.

Where this form came from

The form you received is the HeatAlgo client form - a tool installers use to collect the data for their calculations without a dozen rounds of email. You can fill it in the classic way, or let AI read the values out of documents you upload; you approve every suggestion yourself, and the documents are never stored.

If the technical side interests you, the same material written for professionals is the radiant heating glossary for installers. More answers live in the help center.

Try HeatAlgo for free

A HeatAlgo report follows EN 12831-1 and EN 1264, not ACCA Manual J, and is not accepted for permits or rebates.

HeatAlgo newsletter

New guides, HeatAlgo product changes and offers - straight to your inbox. You confirm the sign-up with a link we send you.

Have a question or feedback?

I reply personally - usually within 24 hours.

Got a similar question? Check the FAQ below ↓

FAQ

Frequently asked questions

What is a floor plan?

A drawing of one story seen from above, as if the house were cut through about 3 feet above the floor and you looked down. It shows the layout and dimensions of the rooms and where the windows and doors are. Floor plans are part of the architectural drawings - usually one per story: basement, first floor, second floor, attic.

What is a building section?

A drawing of the building cut vertically, from foundation to roof. A floor plan shows what is next to what; a section shows what is above what. Ceiling heights and the stacking of floors come from the section, and those give the heated volume. It sits in the same set of drawings as the floor plans.

What is a window and door schedule?

A table of every window and door in the house: tag, size, quantity and often the U-factor. Windows account for a large share of heat loss, so without their sizes the calculation would be guesswork. The schedule is part of the architectural drawings; for a finished house, the window labels (in the US, the NFRC sticker) or a tape measure will do instead.

I do not have the drawings. Can anything still be calculated?

Yes, though your installer will need more from you. Room dimensions measured with a tape, ceiling heights, window and door sizes, and whatever is known about the walls: what they are built from and whether they are insulated - and if so, with what and how thick. Photos from the build, insulation invoices or an energy audit report help too.

Why does my installer ask for an energy rating or energy audit?

Because it often lists the U-factors or R-values of the walls, roof and floor along with the air leakage assumptions - data that would otherwise have to be reconstructed from the drawings or from questions. A rating does not replace the room-by-room heat loss calculation used to size equipment, but it is often the fastest source of input data.

Blog

See also

Guides

Radiant heating glossary for installers: heat loss, U-factor, R-value, delta T

A radiant heating glossary for installers: heat loss, U-factor, R-value, thermal bridges, ACH50, balance point, COP, delta T, outdoor reset and on center.

News

Radiant floor heating from a floor plan: AI draws the sections and loops

Upload a floor plan as PDF, PNG, JPG, HEIC, DWG or DXF, set the scale, and HeatAlgo's AI draws radiant floor heating sections with PEX loop layouts to EN 1264.

Guides

Heat recovery ventilation (HRV) in HeatAlgo (beta): six steps from rooms to the balance and the unit

Design heat recovery ventilator (HRV) systems in HeatAlgo: room airflows in cfm, ducts on floor plans, the unit from EPREL, modes and the air balance.

Guides

Heat loss calculation: what a room-by-room calculation is and what depends on it

A heat loss calculation gives the power a house needs in the coldest hour, room by room, to EN 12831-1. Worked example: 1,100 ft², 15,651 Btu/h.

Guides

How to design radiant floor heating in HeatAlgo - a step-by-step guide

Radiant floor layout tool and calculator in one: upload a floor plan, draw loops yourself or with Algo AI, connect the manifold and download the PDFs.

Guides

How to send the client form and get complete data - a step-by-step guide

How to send the client form in HeatAlgo, from creating the project to accepting your client's data - step by step, screen by screen, no jargon.

Guides

Algo AI assistant in HeatAlgo: what it does, where to find it and its limits

The Algo AI assistant in HeatAlgo: where to open it, how it reads building plans and reviews a project, its two modes, undo, sources and the monthly limit.

Guides

What water temperature does radiant floor heating need? Btu per square foot by floor covering

Radiant floor heat pump or boiler: at 95 °F supply water and 6-inch spacing a slab gives 13.3 Btu/h·ft² under tile, 12.4 under wood, 11.1 under carpet.

Guides

Radiant floor heating layout: tubing spacing on center, and how long a loop can be

Radiant floor heating layout: the area ÷ spacing rule skips the leaders. At 6 in on center it came up 41.7 ft short on one 138 sq ft room.

Guides

Oversized heat pump: why it short cycles and what that costs you

Heat pump short cycling: why a unit 2x too big for the house starts and stops all season, what that costs in efficiency and wear, and how to check the size.

Guides

Radiant floor heating design guide: what a layout should include and how to check one

Radiant floor heating design guide: check room loads, loop schedule and supply water temperature, with a worked 8-loop example in Btu/h, ft and gpm.

Guides

Retrofitting radiant floor heat in an older house: what to measure before you choose a system

Retrofit radiant floor heating: staple-up, panels on top, a thin slab or grooves in a slab. Measure door, threshold and stair heights and room heat loss first.

Guides

Before you get a radiant floor heating quote: what to measure and what to ask the contractor

Before a radiant floor heating installation quote: 6 things to measure and ask, from room-by-room heat loss to oxygen-barrier PEX and slab insulation.

Guides

Where to put a radiant floor heating manifold: basement, closet or one per floor?

Where to put a radiant floor heating manifold: one floor, two positions, and 115.5 ft less tubing in the leaders when it moved to the middle of the hall.

Create a free HeatAlgo account

Register and go from client data to a finished heating project in one place.