
Transmission, ventilation, and thermal bridges per EN 12831-1, U-values per ISO 6946, ground losses per ISO 13370. An empty floor-on-ground perimeter is worked out from the rooms' walls (EN 12831-1 Annex E, ISO 13370).
Product
Algo AI, the assistantAIReads documents, answers, checksHeat loss calculatorHeat loss per EN 12831-1Heat recoveryBetaAir flows and balance to PN-83/B-03430Underfloor heatingLoop design on the floor plan with calculationsHeat pump selectionPreliminary power sizingClient formClient data without phone calls
What it is
HeatAlgo's heat loss calculation runs in the browser and complies with EN 12831-1 (ISO 6946, ISO 13370), room by room - for installers and homeowners. See every wall layer, every U-value, the split between transmission and ventilation losses. Nothing is hidden.
The heat source, the radiators and the underfloor heating follow from the heat loss of one particular house, not from a figure per square metre. Until now, calculating it meant licensed desktop software or commissioning an engineer for every project.
Three minutes on a made-up house: Algo AI reads the floor plan and the building elements, you check every step, and the answer is 4.87 kW for 102 m². The same heat loss calculation the steps below describe.
All recordings →English narration, English and Polish subtitles
From your house plans
Algo AI knows your project - the building elements, the rooms, the building data - and answers in that context. It suggests values, explains the result and watches for gaps. The algorithm always does the calculation, to EN 12831-1.
Meet Algo AI →What U-value for a wall of 24 cm hollow brick and 15 cm EPS?
THINKINGWork it out from the layers, not from a table: 24 cm ceramic hollow brick (λ about 0.30 W/mK) and 15 cm EPS (λ 0.040) give U ≈ 0.21 W/m²K to ISO 6946. Enter both layers on the 'External wall' element - if the EPS label says a different λ, use that and the result recalculates.

Transmission, ventilation, and thermal bridges per EN 12831-1, U-values per ISO 6946, ground losses per ISO 13370. An empty floor-on-ground perimeter is worked out from the rooms' walls (EN 12831-1 Annex E, ISO 13370).
The heat loss calculation implements EN 12831-1 (room-by-room building heat loss) with EN ISO 6946 (thermal resistance of building components) and EN ISO 13370 (ground). The result includes heat losses, U-values, the transmission/ventilation split and an additive thermal-bridge surcharge per EN 12831-1 Annex B.2.1 (ΔU_TB). Useful for quick building assessment and client presentations - a certified energy audit may still be required for formal grant applications. Full compliance covers residential buildings with natural, mechanical, or MVHR ventilation, without air transfer devices (ATDs).
Register, enter the building data, and see a result compliant with EN 12831-1 in minutes.
No payment card. Your projects and data stay in your account.