Balancing underfloor heating: the flow rate of every loop from the room's heat loss - 11 loops worked through

Balancing underfloor heating step by step: from a room's heat loss to the flow meter setting. In a 102 m² house at 40/35 °C the loops need 0.61 to 1.37 l/min.

Founder of HeatAlgo, author of the calculation engine to EN 12831 and EN 1264

Short answer: balancing underfloor heating means setting each loop on the manifold to the flow rate its design gives it, not one figure for all of them. A loop's flow rate follows from the room's heat loss in four steps: the room's heat loss, the heat the water carries, how much the water cools in the loop, and l/h = 0.86 × W / K. In the HeatAlgo reference house - 102.2 m², Warsaw, -20 °C, 15 cm pipe spacing, 40/35 °C flow and return - the eleven loops need from 0.61 l/min in the bathroom to 1.37 l/min in the hall, 10.03 l/min in total.

The article underfloor heating flow meter settings shows that every loop needs a different flow. Here we work out where each of those numbers comes from: from the room's heat loss to what the flow meter should read. Every figure was calculated by HeatAlgo's underfloor heating module (EN 1264-2 and EN 1264-3) for the reference house: tiles in the kitchen, bathroom, hall and plant room, engineered wood in the other rooms, 16×2 pipe, 45 mm of cement screed over the pipe, loops laid at 15 cm across the whole floor.

Balancing underfloor heating in four steps: the hall

The hall has 10.2 m² of tiled floor and one loop. This is how its setting comes about:

  1. The room's heat loss. The heat loss calculation gives the hall 552.9 W, or 54.2 W/m². That is the heat the floor has to give off into the room.
  2. The heat the water carries. The water also gives off heat downwards, through the insulation under the pipes. EN 1264-3 (Formula 13) therefore adds the floor's own heat loss from the calculation again under the pipe, 110 W in the hall, and multiplies the sum by 1 + Ro/Ru - the ratio of the thermal resistance above the pipe to the one below it. In the hall that is 4.5% more: (552.9 + 110) W × 1.045 = 692.5 W.
  3. How much the water cools in the loop. The manifold gives one flow temperature. The plant room (16 °C, 69.7 W/m²) needs 39.3 °C, so the module sets 40 °C for the whole house. The hall manages with 38.7 °C, so its loop may cool the water by more than the design 5 K: the water comes back from the hall at 32.7 °C, cooled by 7.27 K.
  4. The flow rate. 0.86 × 692.5 W / 7.27 K = 81.9 l/h, or 1.37 l/min. That is what the hall loop's flow meter should read.

The quick sum from the room's heat loss at 5 K on every loop gives the hall 1.58 l/min. The module gives less, because at 40 °C the water in the hall may cool by 7.27 K rather than 5 K - even though it carries more heat, with the downward loss added.

The flow rate of every loop: what the flow meters should read

The same sum for all eleven loops at a 40/35 °C flow and return. Where a room has several loops, its heat loss is shared equally, because the loops have the same area and floor covering.

LoopHeat lossFloor's own loss, again underneathHeat in the waterWater cools byFlow meter
Living room, each of 3 loops (wood)446.6 W102.7 W576.5 W8.63 K0.96 l/min
Kitchen (tiles)380.5 W111.0 W514.2 W10 K0.74 l/min
Bedroom, each of 2 loops (wood)376.7 W95.0 W497.0 W9.18 K0.78 l/min
Room 1 and Room 2, 1 loop each (wood)449.5 W124.0 W600.5 W10 K0.86 l/min
Bathroom, 24 °C (tiles)311.3 W99.0 W424.9 W10 K0.61 l/min
Hall (tiles)552.9 W110.0 W692.5 W7.27 K1.37 l/min
Plant room, 16 °C (tiles)418.5 W69.0 W513.5 W6.27 K1.17 l/min

Together the eleven loops need 10.03 l/min, or 0.60 m³/h through the manifold. The hall gets the most water - it loses the most heat per square metre of the rooms heated to 20 °C, and its water cools less than in the other rooms. The bathroom gets the least. The kitchen, both rooms and the bathroom cool the water by 10 K - the most HeatAlgo's module allows for one loop.

No loop here runs at the design 5 K. Set the flow temperature to exactly 39.3 °C and the plant room loop would cool the water by 5 K, and every other setting would move. That is why the flow meter table is worked out for the flow temperature the house actually runs at.

Why not 1.5 l/min on every loop

Eleven loops at 1.5 l/min make 16.5 l/min - 64% more than this house needs. The bathroom loop would get 2.5 times the water the design gives it, and its water would come back warmer. The circulating pump has to move all of that water, and the hall, which needs the water most, gets no more of it. What happens to the hall when its flow meter reads too little is in underfloor heating not working in one room.

How to set the flow meters on the manifold

  1. Run the heating at the design flow temperature and open every actuator (room thermostats turned all the way up).
  2. Set each flow meter to its loop's figure from the table. The flow meter reads l/min, so divide a design figure in l/h by 60.
  3. Go along the manifold a second time. Turning one loop down sends more water to the others, so the first settings move.
  4. Check the total. The flow meters together should give the manifold's flow, here 10.03 l/min. If a loop cannot reach its figure even with its flow meter fully open, the circulating pump gives too little or the loop's resistance is too high - that is one for your installer.

What the table does not tell you

The design flow is the value to set on the flow meter. HeatAlgo's module also gives each loop's pressure drop, but it does not work out valve presettings or size the circulating pump. These are calculations, not measurements, for the reference house with wet underfloor heating in a screed. Your house will give different numbers - the same steps, the same formula. Every input of the reference house is on the page the reference house, calculated in full.

Work out the flow meter table for your own house

In HeatAlgo's underfloor heating design tool every loop gets its heat, its cooling and its flow rate from the same four steps, and the Flow meters table lists them by manifold and port - ready to set on site. A free account shows the full result for one loop; the report gives the table for every loop.

Work out the flow rate of every loop

HeatAlgo newsletter

New guides, HeatAlgo product changes and offers - straight to your inbox. You confirm the sign-up with a link we send you.

FAQ

Frequently asked questions

What does balancing underfloor heating mean?

Setting each loop on the manifold to the flow rate its design gives it: l/h = 0.86 × W / K, where W is the heat the water in the loop carries and K is how much the water cools in the loop. In the HeatAlgo reference house at a 40/35 °C flow and return, the eleven loops need 0.61 l/min (bathroom) to 1.37 l/min (hall), 10.03 l/min in total.

How do I set the flow meters on an underfloor heating manifold?

With the heating running and every actuator open, set each flow meter to its loop's figure from the table, then go along the manifold a second time, because changing one loop shifts the others. The flow meters should add up to the manifold's total flow - 10.03 l/min, or 0.60 m³/h, in the HeatAlgo reference house.

Can I set every loop to 1.5 l/min?

You can, but that is not balancing. In the HeatAlgo reference house 11 loops at 1.5 l/min make 16.5 l/min, 64% more than the 10.03 l/min the design needs, and the bathroom loop would get 2.5 times the water it needs.

Why do the loops in one house cool the water by different amounts?

Because the manifold gives every loop one flow temperature, set by the hardest room. In the HeatAlgo reference house that is the plant room, which needs 39.3 °C. Rooms that manage with cooler water cool it further: the hall by 7.27 K, the kitchen, rooms 1 and 2 and the bathroom by 10 K, so they need less water.

Blog

See also

Releases

What's new: Second opinion, the Radiators module and a new results screen

Check a heat pump quote against your house, see if your radiators work at a low flow temperature, and read every result as a heat map. Plus iPad and phone.

Guides

A second opinion on a heat pump quote: how to compare it with your own house

Step by step: calculate your house's heat loss to EN 12831-1, add the installer's quote and see where the kW difference comes from and what to ask. No verdict.

Guides

Underfloor heating not working in one room? Check heat loss and loop flow first - 5 causes in order

Underfloor heating not working in one room? Check in order: the room's heat loss against the floor's output, loop flow, flow temperature and floor covering.

Releases

Update: underfloor heating drawn for you, the app in five languages and new PDF reports

Algo AI reads the floor plan and the app draws the underfloor heating. The app now speaks German, French and Dutch, and PDF reports have a new print design.

Releases

Update: a bill of materials, one-module reports and Algo AI in every field

Underfloor heating now works out what to order from the merchant, a report can cover one or two modules, and one Algo AI reading fills three modules.

Releases

Update: Algo AI reads the building design, party walls and My library

Algo AI fills the heat loss calculation from the building design, party walls count against the neighbour, and underfloor heating gets a new panel.

Guides

Retrofit underfloor heating on a concrete floor: milling channels or an overlay?

Floor milling cuts channels for water underfloor heating into your existing screed. When the floor suits it, what a quote should list, and the alternatives.

Guides

Retrofitting water-based underfloor heating: what to measure first

A new screed, a dry system or milling? Measure levels at doors, thresholds and stairs, find out the floor layers and check room heat loss. With a worksheet.

Guides

Where to put an underfloor heating manifold: cupboard, under the stairs or central?

Choosing an underfloor heating manifold location: one floor, two positions, the pipe runs and loop lengths HeatAlgo calculated, and what to ask your installer.

Guides

How to check an underfloor heating design: the drawing, the loop schedule and room heat loss

Check the drawings, room calculations, loop details and handover scope in a water-based underfloor heating design. Includes a quote-comparison worksheet.

Guides

Getting an underfloor heating quote: what to prepare and how to compare quotes

Prepare for a water-based underfloor heating quote: floor plans, insulation, floor finishes, heating system and questions for your installer.

News

Underfloor heating from a floor plan: AI draws the sections and loops

Upload a floor plan (PDF, PNG, JPG, HEIC, DWG or DXF): HeatAlgo draws underfloor heating sections, supply runs and the manifold, output and flows to EN 1264.

Releases

Update: simpler plan selection and checkout

Compare plans in one window, unlock a complete project and enter your discount code at checkout.

Guides

Heat recovery ventilation in HeatAlgo (beta): six steps from rooms to the balance and the unit

The six steps of the ventilation module: building, rooms and airflows to PN-83/B-03430, ducts on floor plans, the unit from EPREL, modes and the balance.

Guides

Algo, the AI assistant in HeatAlgo: what it does, where to find it and its limits

Where to open Algo AI, how it reads building documents and reviews a project, the Propose and Automatic modes, undo, files, sources and the monthly limit.

Releases

Update: underfloor heating now computes to EN 1264

Loop output answers to spacing, layout and the drawn pipe; the characteristic from EN 1264-2, each loop's spread and flow from EN 1264-3 - what's new in HeatAlgo.

Guides

Underfloor heating flow temperature with a heat pump: what each floor finish gives at 35-45 °C

Water temperature and floor covering set a floor's output, not its area. Calculated table: what 30, 35, 40 and 45 °C give per m² under tile, wood and carpet.

Guides

Electric underfloor heating loses its subsidy in 2027 - what stays in Czyste Powietrze

From 2027 the programme funds no heating mats, electric boilers, electric radiators or electric underfloor heating. What stays on the list, and what it changes.

Guides

Underfloor heating pipe spacing: 100, 150 or 200 mm, and how long a loop can be

The (area ÷ spacing) × 1.1 formula counts neither the run to the manifold nor the setback from the walls. Here is how far off it is, and how to work out a loop from real geometry.

Guides

Split heat pump ban 2027: what leaves the market, and what stays

No, an installed heat pump does not have to be replaced. From 1 January 2027 split air-to-water units up to 12 kW on GWP 150 or more leave the market.

Releases

Update: data travels between modules, and the app has a new layout

Heat loss calculations and the client form now feed every module, the app has a new layout, and supply runs can cross heated rooms - what's new in HeatAlgo.

Guides

Oversized heat pump: short cycling, and how to check your installer's kW figure

Why a heat pump sized "with a margin" cycles, loses seasonal efficiency and wears its compressor faster - and how to size one from a calculation, not a rule of thumb.

Guides

Installer's glossary: heat loss, U-value, lambda, thermal bridges

Heat loss and equipment sizing terms explained: U-value, lambda, thermal resistance, thermal bridges, n50, bivalent point, SCOP and the heating curve.

Guides

A client's glossary: what the terms in your installer's form mean

Your installer is asking for floor plans, sections and a window schedule? Here is what each of those documents is, why it is needed and where to find it.

Guides

Heat loss calculation, room by room: what it is and why W/m² rules of thumb fail

The design heat loss is the power a house needs in the coldest hour of the year, to EN 12831-1. Worked example: 102.2 m², 4382.07 W. What depends on it, what it costs.

Releases

Update: pump sizing straight from the heat loss calculation

The pump module now reads the project's heat loss calculation directly - no imported copies, a per-room loss breakdown, and the full reasoning behind the selected capacity.

Releases

Update: a new generation of underfloor heating drawings

Spiral and meanders drawn like a working design, consistent rules for any room shape, and editable loop nodes - what's new in HeatAlgo.

Releases

Update: AI fills in project data from building documents

AI reads the building design, window schedule and energy certificate, and you approve the data into the heat loss form - what's new in HeatAlgo.

Guides

How to use the underfloor heating module - a step-by-step guide

Upload a floor plan, draw sections yourself or let Algo AI draw the loops, supply routes and manifold, check the results, and download the report and floor plan as PDFs.

Releases

Update: better underfloor heating design and in-app help

A smoother underfloor heating design workflow, in-app help, a help center and multiple storeys in one project - what's new in HeatAlgo.

Guides

How to send a client the form and get complete data - a guide

From creating the project to accepting the client's data - a simple step-by-step guide, screen by screen, no jargon.

Put room-by-room results behind your heating decision.

Prepare a report for €29 incl. VAT. One payment unlocks every module for your house.

Create an account, add your building data, then buy the report in the app. Editing is never limited. New PDF versions for 7 days from each module's first download.