Underfloor heating screed depth: does a thicker screed reduce output? 30-80 mm calculated

Screed depth for underfloor heating: at 35/30 °C, 15 cm and tiles, 30 mm over the pipe gives 43.7 W/m², 45 mm 41.5, 65 mm 38.8 and 80 mm 36.8.

Founder of HeatAlgo, author of the calculation engine to EN 12831 and EN 1264

Short answer: yes, screed depth changes underfloor heating output. At a 35/30 °C flow and return, 15 cm spacing and tiles, the floor gives 43.7 W/m² with 30 mm of screed over the pipe, 41.5 W/m² with 45 mm, 38.8 W/m² with 65 mm and 36.8 W/m² with 80 mm. An 80 mm screed instead of 45 mm takes 11% of the output - more than laying wood on a standard screed does.

"How long does it take to warm up" is what one heat pump owner asks on a UK forum, and the screed questions that follow are usually about strength, drying and that warm-up time. What an extra centimetre of screed over the pipe costs in heat output rarely comes up, yet it can be calculated.

Why screed over the pipe costs output

Heat from the pipe has to pass through the screed to the covering and on into the room. Every millimetre of screed is extra resistance on that path, just like the covering. The EN 1264-2:2021 characteristic treats both the same way: with the same water, a thicker layer over the pipe means fewer W/m² in the room. Cement screed conducts heat at λ = 1.2 W/(m·K), so 35 mm more of it adds a resistance of 0.03 m²K/W. That is less than the resistance tiles are designed with (0.10 m²K/W), but it sits on the same path, under the covering.

Floor output against screed over the pipe - 35/30 °C, tiles, 15 cm

Cement screed, λ = 1.2 W/(m·K), 16×2 pipe, 20 °C room, EN 1264-2:2021. Scale from 30 W/m².

What that means in practice

An 80 mm screed instead of 45 mm costs 4.7 W/m², or 11%. That is more than swapping tiles for wood on a normal screed, which costs 2.9 W/m². A thick screed usually goes down without a word about output; wood only after a long discussion.

Winning the output back with 80 mm of screed - tiles, 20 °C room
45 mm, 15 cm, 35/30 °C41.5
80 mm, 15 cm, 35/30 °C36.8
80 mm, 10 cm, 35/30 °C40.3
80 mm, 15 cm, 36.5/31.5 °C41.4

Closer spacing does not win it all back: 10 cm with 80 mm gives 40.3 W/m², less than ordinary 15 cm with 45 mm. Only water about 1.5 K warmer does, and that means a heat pump running at a slightly higher temperature all season.

What this number does not show

The calculation is for steady running on a cold design day. It does not show how long a thicker screed takes to warm up and cool down - a different question, about thermal mass, which HeatAlgo does not calculate. It covers wet underfloor heating with the pipe embedded in a cement screed; an anhydrite (calcium sulphate) screed conducts heat differently, and dry systems are calculated by their manufacturer. How output depends on the covering and the spacing is in the guide underfloor heating flow temperature.

Screed thickness: what to check before the pour

  • The depth over the pipe, not the whole screed. Designs and builders often quote the whole layer. What counts for output is the screed above the pipe: with a 16 mm pipe and 6 cm of screed that is about 44 mm.
  • Where the extra depth comes from. Usually an uneven base or services run in the floor. Levelling with insulation rather than screed costs no output.
  • Whether the design uses that depth. The designer should calculate the output for the agreed depth, not the default.
Work out your floor

HeatAlgo newsletter

New guides, HeatAlgo product changes and offers - straight to your inbox. You confirm the sign-up with a link we send you.

FAQ

Frequently asked questions

Does a thicker screed reduce underfloor heating output?

Yes. At a 35/30 °C flow and return, 15 cm spacing and tiles, the floor gives 43.7 W/m² with 30 mm of cement screed over the pipe, 41.5 W/m² with 45 mm, 38.8 W/m² with 65 mm and 36.8 W/m² with 80 mm. 80 mm instead of 45 mm is 11% less heat from the same water - less than wood on a standard screed gives (38.6 W/m²).

How do you win the output back with a thick screed?

With warmer water: with 80 mm of screed the floor gives nearly what it gives with 45 mm only at about 36.5/31.5 °C, 1.5 K higher. Closer spacing is not enough: 10 cm with 80 mm gives 40.3 W/m², still less than 15 cm with 45 mm.

Blog

See also

Answers

How much insulation under underfloor heating? What the minimum sends downwards, calculated

Insulation under underfloor heating: with only the EN 1264-4 minimum (R 1.25) the water sends an extra 18.4% of the room's heat down; on a U 0.30 floor, 7.4%.

Answers

Can underfloor heating be the only heating? Yes, but the hardest rooms set the water temperature

A 102.2 m² house with UFH at 15 cm under tiles: 35/30 °C covers 3 of 8 rooms, 38/33 °C covers 6, and 40/35 °C covers them all. Room by room.

Answers

What size heat pump do I need for a 100 m² house? 4.38 kW calculated, not 8-10

What size heat pump do I need for 100 m²? A calculated 102.2 m² house needs 4.38 kW at -20 °C; sizing looks for 4.91 kW. The 80-100 W/m² rule says 8.2-10.2 kW.

Answers

Underfloor heating flow meter settings: what each loop should read in l/min

Underfloor heating flow meter settings: not 1.5 l/min everywhere. On one floor at 43/38 °C the loops need 0.53 to 1.41 l/min. Formula: 0.86 × W / K.

Answers

How much underfloor heating pipe for a 100 m² house? 799 m in the floor, 1000 m on the order

A 102.2 m² house with UFH at 15 cm: 799.3 m of pipe in the floor, 865.03 m on the materials list, 1000 m bought in coils. The 6.7 m/m² rule misses the runs.

Answers

Is underfloor heating enough in a bathroom? Only just at 35/30 °C, yes at 40/35 °C