Radiator output: where the numbers in the Radiators module come from

Where the Radiators module gets a radiator's output (datasheet, typical, assumed), how it converts it to your temperature and where room loads come from.

Founder of HeatAlgo, author of the calculation engine to EN 12831 and EN 1264

The result of the Radiators module compares two numbers in every room: how much heat the radiators give at the water temperature you chose, and how much heat the room needs. This article says where the module gets both. Every radiator output carries its source in the result: "datasheet", "typical" or "assumed". Every room load comes from the heat loss calculation, from the estimate or from what you typed.

A radiator's output: three sources

"datasheet" - from the radiator's datasheet

Tick "I have the radiator's datasheet" on the radiator and fill in two fields:

  • "Datasheet output at 75/65/20" - the radiator's output in watts at a 75 °C flow, a 65 °C return and a 20 °C room. It is the first row of nearly every maker's datasheet. Type the output of the whole radiator at its height and length.
  • "Exponent n" - the figure from the datasheet that says how fast the output falls as the water gets cooler. Leave it empty and the module uses n = 1.3.

This is the most certain output, because it is your radiator's own.

"typical" - the median of several makers' datasheets

Without a datasheet, a panel radiator with its type entered (10, 11, 20, 21, 22 or 33) gets a typical output. For every type and height we took the output of a 1000 mm radiator and its exponent n from several makers' public datasheets, and used the median. The output scales with the radiator's length. For a height between two heights in the datasheets, the module interpolates between them.

Typical means: an ordinary radiator of that type and height. Yours may give a little more or less. When a room's result is close to the line, check your radiator's datasheet and type its output.

"assumed" - when there is no data

When a radiator has no datasheet output and there is no typical data for it - a column or cast-iron radiator, the kind "Not sure", or a panel radiator with no type - the module counts it as a type 22 panel of its size. A towel rail counts as half a type 11 panel of its size. A type 11, 22 or 33 panel radiator whose height is outside the typical data gets the same general output for its own type. Types 10, 20 and 21 at such a height get no output: the module counts them as 0 W and asks for the datasheet output, because an output borrowed from a type 22 would be several times too high. The exponent n is then 1.3. It is only an assumption so that the room has some output at all - for such a radiator type the datasheet output, or measure the radiator and choose its kind if you can.

The output at the chosen temperature

A datasheet gives the output at 75/65/20, and you check the radiator at another temperature, 50 °C, say. The module converts the output with the radiator characteristic from EN 442:

Φ = Φn · (ΔT / ΔTn)^n

  • Φn - the output at 75/65/20 (from the datasheet, typical or assumed),
  • ΔTn - the excess temperature at 75/65/20, that is 50 K,
  • ΔT - the excess at your temperatures: the mean of the flow and return temperatures minus the room temperature, as EN 442-2 defines it (at 55/45/20, 30 K),
  • n - the radiator's exponent.

The return temperature is the "Flow temperature" minus the "Flow-return difference" from Setup. The room temperature is the temperature typed on the room, and when there is none, the room's temperature from the heat loss calculation or the house's room temperature.

What this output leaves out: mounting factors (niche, cover, connection) and heat from pipes running through the room. The method line under the result and in the report says the same.

With the same characteristic the module finds, for every room, the lowest flow temperature at which its radiators are enough - the "Enough from" column. The highest of those is the house's temperature: "Your radiators heat the house at …".

A room's load: the heat loss calculation or the estimate

The module takes each room's load from one of three places, in this order:

  1. "Typed load" - a value you type on the room. It comes first.
  2. The heat loss calculation. When you bring the rooms in with "Take rooms and loads from Heat loss", every room has its load from the heat loss calculation to EN 12831-1 - worked out from its building elements, windows, ventilation and temperature. When the project uses the heat loss calculation, a room that is not in it gets no estimate: the module does not mix two methods.
  3. The floor-area estimate. Without a heat loss calculation the module estimates the whole house's heat loss from the heated floor area, the building insulation, the design outdoor temperature and the room temperature, and shares it out over the rooms. The screen and the report say beside it: "An estimate from the floor area, not a calculation to EN 12831-1."

The estimate shows the direction - for example that the house needs a higher temperature than you want. To judge one room, and for the swap list, calculate the heat loss. How to do that is in the heat loss calculation guide.

Good to know

  • The module calculates the radiators' output whatever the installation. The pipe network (the Network step) calculates two-pipe systems only, but you can check the radiators in any house.
  • The output is calculated by the algorithm, not by Algo AI. Algo can only enter radiators from a photo or a design - see A radiator from a photo.
  • The result is a radiator check, not an installation design.

HeatAlgo newsletter

New guides, HeatAlgo product changes and offers - straight to your inbox. You confirm the sign-up with a link we send you.

Have a question or feedback?

I reply personally - usually within 24 hours.

Got a similar question? Check the FAQ below ↓

FAQ

Frequently asked questions

What does "typical" mean beside a radiator's output?

That the output is not from your radiator's datasheet. It is the median of several makers' datasheets for a panel radiator of the same type and height. A real radiator may give a little more or less - type its datasheet output when you have it.

What does "assumed" mean?

That the radiator has neither a datasheet output nor typical data - a column or cast-iron radiator, say, or one whose kind you do not know. The module counts it as a type 22 panel of its size. It is the least certain of the three outputs.

Is the floor-area estimate a calculation to EN 12831-1?

No. The floor-area estimate shares an approximate heat loss of the whole house out over the rooms. A calculation to EN 12831-1 works out each room from its building elements, windows and ventilation - that is what the heat loss module does. The screen and the report say beside the estimate: "An estimate from the floor area, not a calculation to EN 12831-1."

Does the output allow for a radiator cover or a niche?

No. The output is calculated without mounting factors (niche, cover, connection) and without heat from pipes. When a radiator sits in a niche or behind a cover, the maker's datasheet says how much less it gives.

Blog

See also

Help

How to check radiators in HeatAlgo: setup, rooms, network and result

The Radiators module step by step: room loads from the heat loss calculation or an estimate, the flow temperature, the pipe network and the swap list.

Help

A radiator from a photo: how Algo AI reads radiators from a photo, a design or a message

How Algo AI fills in radiators from a photo, an old heating design PDF or a message: what it reads, what you type and what happens to the photo.

Help

Full or Simple PDF report: a client version, choosing pages and columns

The "PDF report" window in every module: Full with everything, Simple for the client, and Custom, where you choose the pages, storeys and columns step by step.

Help

Your HeatAlgo account: signing up, signing in, password and language

How to create a free account, confirm your email, sign in, reset your password, switch the app language and what to do when your account is blocked.

Help

Settings: company details, the logo on reports, notifications and privacy

Where to enter company details, how to upload the logo for PDF reports and the client form, how notifications work and what the assistant log switch does.

Help

Subscription, invoices and payments: how to buy, cancel and where to find the invoice

How a purchase works, who issues the invoice, how to add a tax ID, which payment methods work, and how to cancel and resume the subscription.

Help

Troubleshooting: saving, version conflicts, emails, PDF, AI and the browser

Messages about saving and version conflicts, emails that do not arrive, a PDF that does not generate, Algo, expired links, the account and the browser.

Help

PDF reports and the printable floor plan: what they contain, how to download them and what the report number means

Where to download the PDF report from each module, what is on the cover, preview versus full report, the to-scale plans and what to do when a PDF fails.

Help

Projects in HeatAlgo: creating, client details, searching and deleting

What a project is, how to create one, what client details do, how to search projects with Ctrl+K, what the project view shows and how to delete one.

Help

Getting around HeatAlgo: the Start page, the side menu, the top bar and shortcuts

The Start page, the side menu and the top bar, where settings, billing and help are, the Ctrl+K project dialog, the wizards and what works on a phone.

Help

Underfloor heating in HeatAlgo: answers to frequent questions

Why a room is not calculated, what to do with a loop that is too long, loop flows and the spacing warning, editing nodes, storeys and the backdrop.

Help

The heat loss calculation in HeatAlgo: seven steps from documents to result

The seven steps of the heat loss module: the start with Algo, building, ventilation, project constructions, rooms, adjustments and the result with EN 12831-1 compliance.

Help

The client form: answers to frequent questions about setup, sending, corrections and import

How to hide questions and add your own fields, how long the link works, reminders, what the client sees, corrections, acceptance and import.

Help

Heat pump sizing in HeatAlgo: building data, radiators, variants and the result

Starting from the heat loss calculation or by hand, the wizard steps, rooms with radiators, the bivalent point and hot water, three variants, radiator feasibility and annual costs.

Help

Data flows between modules: import from the heat loss calculation and the client form

Which modules take data from which, what the module start screen shows, how updates after changes in the source work and what the import deliberately leaves out.

Help

What is free and what a report unlocks: the free plan, credits and the window for new PDF versions

What a free account shows, what one report unlocks, what credits cost, how the 7-day window for new PDF versions works and when a subscription pays off.

Create a free HeatAlgo account

Register and go from client data to a finished heating project in one place.