Underfloor heating room by room

Underfloor heating for a 25 m² room

A 5 x 5 m room at 150 mm spacing. Below is the real loop geometry - not a rule of thumb from floor area - computed by the same engine that draws loops in the underfloor heating module.

This page assumes: manifold 8 m from the room, 150 mm spacing, 35/30 °C flow and return, 20 °C room temperature. For your own room, use the calculator.

The result

The answer for this room

Loops
2
Pipe in total
172.1 m
Of which the run
15.6 m

A single loop here would be 172.1 m against a recommended limit of 100 m per circuit, so the engine splits this room into 2. A longer circuit means more pressure drop, and the harder it is to balance against the others on the same manifold.

The loop in a 5 x 5 m room

FlowReturnRun to manifoldPattern: spiral · to scale, the run continues off-frame

Spacing

How spacing changes the pipe length

The same 5 x 5 m room at five spacings. The run to the manifold is counted separately.

SpacingIn the roomRunPipe in totalLoops
100 mm233.4 m15.7 m249.1 m3
150 mm156.5 m15.6 m172.1 m2
200 mm118.4 m15.6 m134.0 m2
250 mm96.1 m15.7 m111.8 m2
300 mm80.3 m15.7 m96.0 m1

The run is the distance from the manifold to the room and back, at 8 m. The table describes ONE circuit - split the room and every loop carries its own run, so the pipe order grows with it.

Why the (area ÷ spacing) × 1.1 formula is wrong

Output

How much heat 25 m² of floor delivers

At 35/30 °C and 150 mm spacing. The covering decides it: the higher its thermal resistance, the less heat reaches the room.

CoveringOutput per m²Whole room (25 m²)
Tile50.0 W/m²1,250 W
Vinyl44.6 W/m²1,115 W
Wood39.1 W/m²978 W
Carpet35.7 W/m²893 W

This is what the floor delivers at these settings - not the room's heat loss. Whether one covers the other is settled by a heat load calculation for the whole building.

How flow temperature changes these figures

The set

Other room sizes

The same calculation for the other rooms in this set.

See the underfloor heating module

FAQ

Frequently asked questions

How many loops does a 25 m² room need?

At 150 mm spacing with the manifold 8 m from the room, the engine gives 2 loops, because a single circuit would be 172.1 m including the run, against a recommended limit of 100 m. Changing the spacing or the manifold distance changes that number - the table above shows by how much.

How many metres of pipe for a 25 m² room?

156.5 m in the room itself at 150 mm spacing, plus the run to the manifold. The pipe does not run right up to the wall - it is set back by 100 mm - so the result is lower than floor area divided by spacing.

Are these figures computed or estimated?

Computed. The drawing and the lengths come from the same geometry engine that lays out loops in the HeatAlgo underfloor heating module, and the output per m² from the hydraulics engine. The values are committed to the repository and a test compares them against a live engine run, so a change in the engine breaks the test instead of quietly changing this page.

Your room has different dimensions

The calculator takes any rectangle and draws the loop straight away, with no account. For a whole house, room by room, the underfloor heating module does it in the app.