Radiant floor heating not heating one room? Check heat loss and loop flow first - 5 causes in order

Radiant floor heating not heating one zone? Check in order: the room's heat loss against the floor's output, loop flow in gpm, water temperature and flooring.

Founder of HeatAlgo, author of the calculation engine to EN 12831 and EN 1264

Short answer: when radiant floor heating is not heating one room, start with two numbers: how much heat that room loses per square foot of floor, and how much water its loop gets. In the HeatAlgo reference house - 1,100 ft², a -4 °F design day, tubing at 6 in on center - 104/95 °F water covers the heat loss in all 8 rooms. Turn the water down to 100/91 °F and the hall goes cold first: it loses 17.2 Btu/h·ft², and its tile floor puts out 16.4 Btu/h·ft². The same hall also goes cold with 104 °F water if its flow meter drops below 0.29 gpm.

When one zone stays cool and the rest of the house is warm, the quick advice is to raise the water temperature or "open every flow meter all the way". Sometimes that works, but it does not tell you what the cause was. Here are five things to check, in this order - the first two need only the figures from the design and a look at the manifold.

Every figure in this article was calculated by the HeatAlgo engine for the reference house: tile in the kitchen, bathroom, hall and mechanical room, engineered wood in the other rooms, a 9 °F drop across each loop, EN 1264-2:2021.

1. Can the floor in this room cover its heat loss at all?

Every room has its own heat loss from a room-by-room load calculation, in Btu/h. Divide it by the floor area and you get the Btu/h·ft² the floor has to put out. What it actually puts out depends on the water temperature, the tubing spacing and the flooring. If the first number is bigger than the second, the room will be cool however you set everything else.

RoomHeat lossFloor at 104/95 °FFloor at 100/91 °F
Living room (wood)15.2 Btu/h·ft²17.2 Btu/h·ft²15.2 Btu/h·ft²
Bedroom (wood)14.8 Btu/h·ft²17.2 Btu/h·ft²15.2 Btu/h·ft²
Rooms 1 and 2 (wood)12.0 Btu/h·ft²17.2 Btu/h·ft²15.2 Btu/h·ft²
Kitchen (tile)12.1 Btu/h·ft²18.6 Btu/h·ft²16.4 Btu/h·ft²
Bathroom, 75 °F (tile)12.2 Btu/h·ft²17.6 Btu/h·ft²14.9 Btu/h·ft²
Hall (tile)17.2 Btu/h·ft²18.6 Btu/h·ft²16.4 Btu/h·ft²
Mechanical room, 61 °F (tile)22.1 Btu/h·ft²22.9 Btu/h·ft²20.7 Btu/h·ft²

At 100/91 °F two rooms come up short: the hall (17.2 against 16.4 Btu/h·ft²) and the mechanical room (22.1 against 20.7 Btu/h·ft²). The living room only just makes it, by a fraction the table rounds away. The hall loses the most heat per square foot of any room heated to 68 °F. That is the typical "one cold room": nothing is broken, the floor simply has nothing more to give.

2. Is the loop getting the water it needs?

The second number is the flow. The water in a loop carries heat to the room, and how much of it you need follows from that heat and how much the water is meant to cool: gpm = Btu/h ÷ (500 × ΔT °F). For the hall that is 1,887 Btu/h ÷ (500 × 9 °F) = 0.42 gpm - the most of any loop in the house. HeatAlgo's radiant floor module also counts the heat the floor loses downward, so its figure for the loop is slightly higher.

What happens when the hall's flow meter reads less (104 °F supply):

Hall loop flowHall floor puts outHall heat loss
0.42 gpm18.4 Btu/h·ft²17.2 Btu/h·ft²
0.40 gpm18.2 Btu/h·ft²17.2 Btu/h·ft²
0.26 gpm16.9 Btu/h·ft²17.2 Btu/h·ft²
0.21 gpm15.9 Btu/h·ft²17.2 Btu/h·ft²
0.16 gpm14.6 Btu/h·ft²17.2 Btu/h·ft²

Less water cools down more in the loop, so the floor's average temperature falls. Below 0.29 gpm the hall stops keeping up, even though the water going in is still at 104 °F. Setting every loop to the same number happens to be enough for this hall - but a flow meter turned down during balancing, or left low after startup, is enough to make it cold. How to work out each loop's flow is in a separate article: what radiant floor flow meters should read.

3. Is the water temperature the one in the design?

The manifold gives every loop the same water temperature. If the reset curve is set lower than the design assumes, the rooms with the highest heat loss per square foot go cold first:

  • at 104/95 °F the floor covers the heat loss in 8 of 8 rooms,
  • at 100/91 °F in 6 of 8,
  • at 95/86 °F in 3 of 8.

If several rooms are cool at once, start with the water temperature, not the flow meters. If it is one room, go back to steps 1 and 2. Why every room needs different water is covered in the radiant floor heating water temperature guide.

4. What is on the floor?

Flooring is a thermal resistance that all the heat has to pass through. With 104/95 °F water the hall floor puts out 18.6 Btu/h·ft² under tile, 17.2 Btu/h·ft² under engineered wood, and 15.6 Btu/h·ft² under carpet - less than the 17.2 Btu/h·ft² the hall loses. A thick rug over much of the floor, or carpet laid years later, can turn a warm room into a cold one on its own.

5. The rest: air, actuators, thermostat, first warm-up

These causes are real, but no figure from the design can check them:

  • Air in the loop - the loop is clearly cooler than its neighbors with its flow meter open. Ask your installer to purge it.
  • An actuator or thermostat - the loop does not heat at all, or only sometimes. Check with your installer that the actuator on the manifold opens.
  • A new slab or pour - the first warm-up follows the contractor's schedule. Ask your installer which stage it is at.

Radiant floor heating not heating? Check it on your own house

Steps 1 and 2 are two numbers per room, and both come from the design. In HeatAlgo's radiant floor heating design tool every room shows the floor's output next to its heat loss and flags a shortfall where the floor does not cover it, and the Flow meters table gives the flow to set for each loop on the manifold.

Check floor output and flow for every loop

A HeatAlgo report follows EN 12831-1 and EN 1264, not ACCA Manual J, and is not accepted for permits or rebates.

HeatAlgo newsletter

New guides, HeatAlgo product changes and offers - straight to your inbox. You confirm the sign-up with a link we send you.

FAQ

Frequently asked questions

Why is my radiant floor heating not heating one room?

Usually because the room loses more heat per square foot than its floor puts out: in the HeatAlgo reference house the hall loses 17.2 Btu/h·ft², and with 100/91 °F water its tile floor puts out 16.4 Btu/h·ft². The other common cause is a loop that gets too little water.

Radiant floor one room cold, the rest warm: what do I check first?

The flow meter on that room's loop, because every loop needs a different flow. In the HeatAlgo reference house the hall needs 0.42 gpm, the most in the house, and with 104 °F supply water its floor stops covering its heat loss below 0.29 gpm. Each loop's flow follows from its heat and how much the water cools: gpm = Btu/h ÷ (500 × ΔT °F).

Will turning up the water temperature fix one cold room?

It helps if the water is too cool for the hardest room: in the HeatAlgo reference house the floor covers the heat loss in 3 of 8 rooms at 95/86 °F, 6 of 8 at 100/91 °F and all of them at 104/95 °F. It does not replace flow: a loop starved of water stays cool, and hotter water lowers the heat pump's efficiency for the whole house.

Can a rug keep radiant floor heating from warming a room?

It can: the hall's tile floor puts out 18.6 Btu/h·ft² with 104/95 °F water; the same floor with carpet on it puts out 15.6 Btu/h·ft² - less than the 17.2 Btu/h·ft² the hall loses. A thick rug over much of the floor works the same way.

Blog

See also

Releases

Update: radiant floor heating drawn for you, the app in five languages and new PDF reports

Algo AI reads the floor plan and the app draws the radiant floor heating. The app now speaks German, French and Dutch, and PDF reports have a new print design.

Guides

Radiant heating glossary for installers: heat loss, U-factor, R-value, delta T

A radiant heating glossary for installers: heat loss, U-factor, R-value, thermal bridges, ACH50, balance point, COP, delta T, outdoor reset and on center.

Guides

Heating glossary for homeowners: what your installer's form asks for

A heating glossary for homeowners: floor plans, sections, window schedules, U-factor, R-value and radiant floor heating - what each is and where to find it.

News

Radiant floor heating from a floor plan: AI draws the sections and loops

Upload a floor plan (PDF, PNG, JPG, HEIC, DWG or DXF): HeatAlgo draws radiant floor sections, supply routes and the manifold, with output and flows to EN 1264.

Guides

Heat recovery ventilation (HRV) in HeatAlgo (beta): six steps from rooms to the balance and the unit

Design heat recovery ventilator (HRV) systems in HeatAlgo: room airflows in cfm, ducts on floor plans, the unit from EPREL, modes and the air balance.

Guides

Heat loss calculation: what a room-by-room calculation is and what depends on it

A heat loss calculation gives the power a house needs in the coldest hour, room by room, to EN 12831-1. Worked example: 1,100.07 ft², 14,952.24 Btu/h.

Guides

How to design radiant floor heating in HeatAlgo - a step-by-step guide

Radiant floor layout tool and calculator in one: upload a floor plan, draw loops yourself or let Algo AI draw the loops, supply routes and manifold, then download the PDFs.

Guides

How to send the client form and get complete data - a step-by-step guide

How to send the client form in HeatAlgo, from creating the project to accepting your client's data - step by step, screen by screen, no jargon.

Guides

Algo AI assistant in HeatAlgo: what it does, where to find it and its limits

The Algo AI assistant in HeatAlgo: where to open it, how it reads building plans and reviews a project, its two modes, undo, sources and the monthly limit.

Guides

What water temperature does radiant floor heating need? Btu per square foot by floor covering

Radiant floor heat pump or boiler: at 95 °F supply water and 6-inch spacing a slab gives 13.3 Btu/h·ft² under tile, 12.4 under wood, 11.1 under carpet.

Guides

Radiant floor heating layout: tubing spacing on center, and how long a loop can be

Radiant floor heating layout: the area ÷ spacing rule skips the leaders. At 6 in on center it came up 41.7 ft short on one 138 sq ft room.

Guides

Oversized heat pump: why it short cycles and what that costs you

Heat pump short cycling: why a unit 2x too big for the house starts and stops all season, what that costs in efficiency and wear, and how to check the size.

Guides

Radiant floor heating design guide: what a layout should include and how to check one

Radiant floor heating design guide: check room loads, loop schedule and supply water temperature, with a worked 8-loop example in Btu/h, ft and gpm.

Guides

Retrofitting radiant floor heat in an older house: what to measure before you choose a system

Retrofit radiant floor heating: staple-up, panels on top, a thin slab or grooves in a slab. Measure door, threshold and stair heights and room heat loss first.

Guides

Before you get a radiant floor heating quote: what to measure and what to ask the contractor

Before a radiant floor heating installation quote: 6 things to measure and ask, from room-by-room heat loss to oxygen-barrier PEX and slab insulation.

Guides

Where to put a radiant floor heating manifold: basement, closet or one per floor?

Where to put a radiant floor heating manifold: one floor, two positions, and 114.8 ft less tubing in the leaders when it moved to the middle of the hall.

Put room-by-room results behind your heating decision.

Prepare a report for $32. One payment unlocks every module for your house.

Create an account, add your building data, then buy the report in the app. Editing is never limited. New PDF versions for 7 days from each module's first download.